Description
FDC L Series High Limit Control FDC-L91 is a 1/16DIN control designed to provide limit protection in process applications.
Up to three discreet setpoints, two outputs, fast scan rates, and user-friendly prompts make it the right choice for safety protection. The FDC-L91 offers a full range of universal inputs. Power supply selections of 90-264 VAC (std) or 11-26 VAC/VDC allow the FDC-L91 to be used virtually anywhere.
Output selections include Relay, SSR Drive, or Triac. Optional features such as a second latching relay, DC power supply, remote reset, or communications offer maximum flexibility for demanding applications. The FDC-L91 display can be configured for PV, HSP, LSP, or Safe, offering the simplicity required by operations personnel.
L91 Specification Review
- Power Input:
- 90-264VAC
- 11-26 VAC/11-36 VDC optional
- Input sample rate – 5 scans/second
- Input:
- Universal Thermocouple & RTD
- Special Order linear mA/VDC [FM approval applies only to units with thermocouple or RTD input]
- Event Input – Optional: Configurable as a Remote Reset or to Lock all parameters.
- Universal Thermocouple & RTD
- Limit Control Output #1 – Latching: Configurable as High Alarm, Low Alarm or combination High-Low Alarm Setpoint with one digital output. Available Digital Outputs:
- Relay: 2A/240 VAC resistive Form C [spdt]
- ssr driver: 5VDC/30mA
- Triac: 1A/240 VA
- Output #2 is available with one of the following options: Digital Output [relay, triac or ssr driver] transmitter power supply, communications and Event Input for remote reset & Lock.
- Digital Outputs are the same as output #1 except the relay is Form A [spst].
- Transmitter Power Supply [Isolated];
- 20 VDC/25mA
- 12 VDC/40mA
- 5 VDC/80mA
- Linear Retransmission:
- Process or Setpoint Values
- 0-5/1-5/0-10 VDC, 0-20/4-20mA
- RS485 Modbus Communication with access to all parameters.
- Configurable Display when not in alarm condition HSP, LSP, SP2, PV and word SAFE.
- When in Alarm display defaults to PV with output 1 annunciation energized.